Power Transformer Efficiency Calculator

A transformer loses a fixed core loss whenever it is energised and a copper loss that grows with the square of load. Efficiency is output ÷ (output + both losses).

Also called: Transformer loss calculator

  • Last updated
  • Formula tested against reference values

Your numbers

From the test certificate or datasheet (open-circuit test).

From the short-circuit test at rated current.

Result

Efficiency
—

Calculating…

Output power
—
Total losses
—
Copper loss at this load
—
Load for maximum efficiency
—

How to use this calculator

  1. Enter or choose rating.
  2. Enter or choose load.
  3. Enter or choose load power factor.
  4. Enter or choose no-load (core) loss.
  5. Enter or choose full-load copper (load) loss.
  6. The efficiency updates as you type. Use Copy result or Share to keep it.

Method

Output = kVA × x × pf; Copper loss = Pcu,FL × x²; η = Output ÷ (Output + Pcore + Pcu,FL × x²) × 100; Maximum efficiency at x = √(Pcore ÷ Pcu,FL)

x
load as a fraction of rating
pf
load power factor
Pcore
no-load (iron) loss
Pcu,FL
copper loss at rated load

Worked example

  1. Output: 100 kVA × 1 × 0.8 = 80 kW.
  2. Losses: 1,000 W core + 1,500 W copper = 2,500 W.
  3. Efficiency: 80 ÷ (80 + 2.5) = 96.97%. Maximum efficiency at √(1000 ÷ 1500) = 81.6% load.

At full load and 0.8 power factor the transformer is 96.97% efficient; its efficiency peaks at about 82% load, where copper loss equals core loss.

What the result means

Because core loss never stops, a lightly loaded transformer can be surprisingly inefficient over a year. For energy over time, weight the losses by how many hours the transformer spends at each load (all-day efficiency).

Assumptions and limits

  • Copper loss scales with the square of current; core loss is constant at rated voltage.
  • Stray and dielectric losses are included in the two test figures.
  • Temperature correction of copper loss and harmonic loads are not modelled.

Questions

Why does power factor change efficiency?

Losses depend on current (kVA), but output is measured in kW. A lower power factor means less useful output for the same losses.

When is a transformer most efficient?

When the variable copper loss equals the fixed core loss, at a load of √(core ÷ full-load copper loss).