Three-Phase Power Calculator

In a balanced three-phase system, real power is √3 × line voltage × line current × power factor. Use it either way: amps to kW, or kW to amps.

Also called: 3-phase power calculator · kW to amps calculator (three-phase) · Three-phase current calculator

  • Last updated
  • Formula tested against reference values

Your numbers

Find

Example value: from the motor nameplate or a power meter; 1 for purely resistive loads.

Result

Result
—

Calculating…

Real power
—
Line current
—
Apparent power
—
Reactive power
—

How to use this calculator

  1. Enter or choose find.
  2. Enter or choose line-to-line voltage.
  3. Enter or choose power factor.
  4. The result updates as you type. Use Copy result or Share to keep it.

Method

P = √3 × V_L × I_L × PF; S = √3 × V_L × I_L; Q = S × sin(arccos PF); I_L = P ÷ (√3 × V_L × PF)

V_L
line-to-line voltage
I_L
line current
PF
power factor
S
apparent power
Q
reactive power

Worked example

  1. S = √3 × 400 × 10 = 6,928 VA = 6.928 kVA.
  2. P = 6.928 × 0.85 = 5.889 kW.
  3. Q = 6.928 × √(1 − 0.85²) = 6.928 × 0.5268 = 3.65 kVAR.

A balanced 400 V three-phase load drawing 10 A at 0.85 power factor uses 5.889 kW.

What the result means

Use current-from-power to size cables and protective devices, then apply the derating and starting-current rules in your local wiring regulations.

Assumptions and limits

  • The load is balanced across the three phases.
  • Voltage is line-to-line (e.g. 400 V, not the 230 V phase-to-neutral value).
  • Unbalanced loads need per-phase calculation.
  • Motor starting currents are several times running current and are not included.

Questions

Where does √3 come from?

In a three-phase system the line-to-line voltage is √3 times the phase voltage, so total power 3 × V_phase × I equals √3 × V_line × I.

What if I only know phase-to-neutral voltage?

Multiply it by √3 (about 1.732) to get line-to-line voltage; 230 V phase voltage gives about 400 V line voltage.