AC Annual Running Cost Calculator

An air conditioner’s electrical input is its cooling capacity divided by its efficiency ratio (EER). Multiply by the hours it runs and the share of time the compressor works hard to get yearly kWh.

Also called: Air conditioner running cost calculator · AC electricity cost calculator

  • Last updated
  • Formula tested against reference values

Your numbers

I know the
Capacity unit

From the energy label. Seasonal ratios (SEER, ISEER) give a seasonal average instead.

EER unit

Example value: the average share of full input power over the hours it is on. Use 100% for a measured average draw.

Example tariff — enter your own unit rate.

Result

Running cost per year
—

Calculating…

Electricity per year
—
Full-load input power
—
Average cost per hour of use
—
Average per month
—

How to use this calculator

  1. Enter or choose i know the.
  2. Enter or choose hours used per day.
  3. Enter or choose days used per year.
  4. Enter or choose average load.
  5. Enter or choose electricity price per kWh.
  6. The running cost per year updates as you type. Use Copy result or Share to keep it.

Method

Input kW = Cooling capacity (kW) ÷ EER (W/W); kWh per year = Input kW × Load% × Hours × Days; Cost = kWh × Price (1 kW = 3,412.142 BTU/h)

EER
cooling output divided by electrical input (W/W); a rating in BTU/h per W is divided by 3.412142
Load%
average share of full input power while switched on

Worked example

  1. Input power: 3.5 kW ÷ 3.5 = 1 kW.
  2. Energy: 1 kW × 70% × 8 h × 120 days = 672 kWh.
  3. Cost: 672 × 0.25 = 168 a year.

A 3.5 kW air conditioner with an EER of 3.5, used 8 hours a day for 120 days, costs about 168 a year at 0.25 per kWh.

What the result means

The load figure matters most: an inverter unit in a well-insulated room may average well under its rated input. For a better estimate, measure a typical day with a plug-in or smart meter and use that average with 100% load.

Assumptions and limits

  • Efficiency and load are constant over the season.
  • The tariff is a flat rate per kWh.
  • Real consumption depends on outdoor temperature, insulation, thermostat setting and the unit’s part-load behaviour.

Questions

What is 1 ton of cooling in kW?

One refrigeration ton is 12,000 BTU/h, about 3.517 kW of cooling. Choose BTU/h and enter 12,000 per ton.

EER or SEER?

EER is measured at one test condition; seasonal ratios (SEER, ISEER) average over a typical season and usually give a more realistic yearly figure.