Heat Pump COP Calculator

COP is heat delivered divided by electricity used: a COP of 3 gives 3 kWh of heat per kWh of electricity. The Carnot limit shows the theoretical best for your temperatures.

Also called: Coefficient of performance calculator · Heat pump efficiency calculator

  • Last updated
  • Formula tested against reference values

Your numbers

Measured or from the datasheet at your conditions.

From an energy assessment or past fuel bills × boiler efficiency.

Example rate: enter your own.

Result

Coefficient of performance (COP)
—

Calculating…

Carnot (ideal) COP
—
Share of the Carnot limit achieved
—
Electricity per year at this COP
—
Running cost per year at this COP
—

How to use this calculator

  1. Enter or choose heat output.
  2. Enter or choose electrical input.
  3. Enter or choose output (flow) temperature.
  4. Enter or choose source temperature (outdoor air or ground).
  5. Enter or choose heat needed per year.
  6. The coefficient of performance (COP) updates as you type. Use Copy result or Share to keep it.

Method

COP = Heat output ÷ Electrical input; COP(Carnot) = T_hot ÷ (T_hot − T_cold) in kelvin; Electricity per year = Heat needed ÷ COP

T_hot
output temperature + 273.15
T_cold
source temperature + 273.15

Worked example

  1. COP = 8 ÷ 2.5 = 3.2.
  2. Carnot COP = 308.15 ÷ (35 − 5) = 10.27, so the unit reaches 3.2 ÷ 10.27 = 31.15% of the ideal.
  3. Yearly electricity = 10,000 ÷ 3.2 = 3,125 kWh × 0.25 = 781.25.

Delivering 8 kW of heat from 2.5 kW of electricity is a COP of 3.2, so 10,000 kWh of heat costs about 781 a year.

What the result means

COP falls as the gap between source and output temperature grows, which is why low flow temperatures (larger radiators, underfloor heating) improve efficiency. A single COP measurement is a snapshot; the seasonal average (SCOP) is what sets yearly cost.

Assumptions and limits

  • The COP entered applies to the whole year when estimating running cost.
  • Defrost cycles, backup heaters and pump energy reduce real seasonal efficiency.

Questions

What is the difference between COP and SCOP?

COP is measured at one set of conditions; SCOP (seasonal COP) averages performance across a heating season and is the better guide to annual cost.

Can COP be higher than the Carnot COP?

No. If a measurement exceeds it, the heat or power readings are wrong.