Voltage Drop Calculator

Current flowing through a cable’s resistance loses some voltage before it reaches the load. The drop grows with current and length and falls as the conductor gets thicker.

Also called: Cable voltage drop calculator · Wire voltage drop calculator

  • Last updated
  • Formula tested against reference values

Your numbers

Line-to-line voltage for three-phase.

Length in
Conductor size as
Conductor

Resistance rises about 0.4% per °C. Loaded cables often run at 50–90 °C.

Result

Voltage drop
—V

Calculating…

Drop as a share of supply
—
Voltage at the load
—
Conductor cross-section
—
Conductor resistance
—
Power lost in the cable
—

How to use this calculator

  1. Enter or choose system.
  2. Enter or choose supply voltage.
  3. Enter or choose load current.
  4. Enter or choose one-way cable length.
  5. Enter or choose length in.
  6. The voltage drop updates as you type. Use Copy result or Share to keep it.

Method

R = ρ × L ÷ A × (1 + α(T − 20 °C)); DC and single-phase: Vd = 2 × I × R; three-phase: Vd = √3 × I × R

ρ
resistivity at 20 °C: copper 0.017241 Ω·mm²/m (1/58, 100% IACS), aluminium 0.028265 (61% IACS)
L
one-way length (m)
A
cross-section (mm²); AWG uses d = 0.127 mm × 92^((36 − n)/39)
α
temperature coefficient: copper 0.00393, aluminium 0.00403 per °C
I
load current (A)

Worked example

  1. Resistance of one conductor: 0.017241 × 30 ÷ 2.5 = 0.2069 Ω.
  2. Single-phase current flows out and back: Vd = 2 × 16 × 0.2069 = 6.62 V.
  3. 6.62 ÷ 230 = 2.88% of the supply, leaving 223.38 V at the load.

16 A over 30 m of 2.5 mm² copper drops about 6.6 V (2.9%) on a 230 V single-phase circuit at 20 °C.

What the result means

Wiring rules set maximum drops, often a few per cent depending on the country and the type of circuit. If the result is close to your limit, use a larger conductor or a shorter route, and repeat the calculation at the cable’s operating temperature.

Assumptions and limits

  • Resistive drop only: cable reactance and load power factor are ignored, which is accurate for small and medium cables at mains frequency.
  • Three-phase loads are balanced.
  • Cable sizing must also meet current-carrying capacity, fault protection and installation rules set by your local wiring regulations.
  • Very large conductors (above about 50 mm²) need reactance included; use the manufacturer’s mV/A/m data.

Questions

Why multiply by 2 for single-phase?

Current goes out along one conductor and returns along the other, so the cable length is effectively doubled. In a balanced three-phase circuit the factor is √3 instead.

Which temperature should I use?

For a quick check use 20 °C. For a design check use the cable’s maximum operating temperature (for example 70 °C for PVC insulation), which raises copper resistance by about 20%.

Please note: Quantities are estimates. Confirm requirements with your engineer or supplier before ordering materials.